Localizar produto:
     Logotipo_Fluke.GIF (498 bytes)   
FLUKE - 1550 MEGOHMMETER
 
Digital insulation testing up to 5000 Volts

The Fluke 1550 is a digital MegOhmMeter capable of testing switchgear, motors, generators, and cables at up to 5000 V dc.

Electrical Specifications
Insulation Resistance Measurement
Test Voltage (dc) Range Accuracy
(± reading)
500 V 200 kW to 10 GW
10 GW to 100 GW
5 %
20 %
1000 V 200 kW to 20 GW
20 GW to 200 GW
5 %
20 %
2500 V 200 kW to 50 GW
50 GW to 500 GW
5 %
20 %
5000 V 200 kW to 100 GW
100 GW to 1 TW
5 %
20 %
Short circuit current Greater than 1 mA and less than 2 mA
Bar graph range 0 to 1 TW
Insulation test voltage accuracy -0 % to + 10 % at 1 mA load current
Induced ac mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per µF
Leakage current Range: 1 nA to 2 mA
Accuracy: ±(5 % + 2 nA)
Capacitance
measurement
Range: 0.01 µF t 15.00 µF
Accuracy: ± (15 % rdg + 0.03 µF)
Live circuit Indicator Range: 30 V to 600 V ac/dc, 50/60 Hz
Accuracy: ± (5 % + 2 V)
Timer 0 to 99 minutes; settable in 1 minute increments; indicated to within 1 second
Ramp   0 % to 100 % of selected test voltage, or until breakdown
 

All stated accuracy tolerances apply to the temperature
range 0 °C to 35 °C (32 °F to 95 °F). For operating
temperatures between -20 °C to 0 °C (-4 °F to 32 °F)
and 35 °C to 40 °C (95 °F to 104 °F), these tolerances double.


Mechanical Specifications
Dimensions
(L x W x H)
170 mm x 242 mm x 330 mm
(6.7 in x 9.5 in x 13.0 in)
Weight
(with battery)
4 kg (8.8 lbs)


Power
Battery type 12 volt, lead-acid, rechargeable
Charger input (AC) 85 to 250 V ac 50/60 Hz 50 VA
Charger input (DC car adapter) 10 to 15 V dc, 30 VA
Battery life (typical)
Note: At higher temperatures,
the battery requires more
frequent charging.
Test voltage Number of tests
500 V 3600
1 kV 3200
2.5 kV 2500
5 kV 1500


Environmental Specifications
Operating temperature -20 °C to 40 °C (-4 °F to 104 °F)
Storage temperature -20 °C to 65 °C (-4 °F to 149 °F)
Relative Humidity 80 % at 31 °C decreasing linearly to 50 % at 40 °C
Operating altitude 0 to 2000 meters
Enclosure sealing IP-40
Shock, vibration MIL-PRF-28800F, Class II
EMI immunity EN 61326
Safety EN 61010-1, CAT III, 600 V,
EN61557, PARTS 1 & 2
Input Overload Protection 600 V ac continuous


Software Specifications
Quicklink 1550 Software   Requires a PC running Windows® 95, 98, Me, 2000, NT4.0
2-year warranty
     Link_Volta.GIF (1048 bytes)

 
MULTITEC - Instrumentos de Medição Ltda.
Rua Pedro Ernesto, 70-Lj - Saúde - Rio de Janeiro - RJ CEP:. 20220-350
TEL: (0XX21) 2233-3283 / 2516-2153 :: FAX: (0XX21) 2233-3847